Damage and Handling Methods of Metal Oxide Surge Arresters
The damage of metal oxide surge arresters mainly occurs in two aspects.
a. Aging of zinc oxide valve plates.
b. Flashover at the interface between the valve plate and the external insulating material. The specific phenomena include the following.
① Phenomenon: Abnormally elevated DC reference voltage.
Conclusion: Nonlinearity of zinc oxide valve plates has decreased.
Treatment: Replace the entire surge arrester, or replace the zinc oxide valve plates.
Cause: The rated voltage of the surge arrester is too low; the valve plates are not qualified.
② Phenomenon: Abnormally decreased DC reference voltage.
Conclusion: Zinc oxide valve plates have aged.
Treatment: Replace the entire surge arrester, or replace the zinc oxide valve plates.
Cause: The rated voltage of the surge arrester is too low; the valve plates withstand the number and energy of discharges is excessive.
③ Phenomenon: Abnormally increased leakage current.
Conclusion: The interface between the valve plate and the external insulating material is damp, or the quality of the zinc oxide valve plates is poor.
Treatment: Replace the entire surge arrester, or remove the surge arrester components, dry them and re-seal them.
Cause: The seal of the surge arrester fails; the silicone rubber outer jacket of the surge arrester deteriorates; there is a problem with the valve plates or assembly process of the surge arrester.
④ Phenomenon: The leakage current is extremely large, causing difficulties in closing the switch.
Conclusion: The valve plates have been damaged.
Treatment: Replace the entire surge arrester.
Cause: The surge arrester was not detected and repaired in time after aging; it has endured a large current impact (close-range lightning strike or large-power capacitor discharge); the seal of the surge arrester is poor.
⑤ Phenomenon: The surge arrester bursts or the surface turns black.
Conclusion: The valve plates have cracked or perforated.
Treatment: Replace the entire surge arrester.
Cause: The surge arrester was not detected and repaired in time after aging; it has endured a large current impact (close-range lightning strike or large-power capacitor discharge); the seal of the surge arrester is poor.