Fault Handling of Valve-Type Surge Arresters

1. When the weather is normal but cracks are found in the porcelain casing of the surge arrester, the operation should be immediately stopped. The faulty phase surge arrester should be withdrawn from operation and a qualified surge arrester should be replaced. If cracks are found in the porcelain casing during a thunderstorm, the operation should be maintained until after the thunderstorm, and then the handling should be carried out. If flashover occurs due to cracks in the porcelain casing of the surge arrester but does not cause system grounding, the faulty phase surge arrester should be shut down under possible conditions.
2. Abnormalities inside the surge arrester or cracking of the casing. This phenomenon may cause system grounding faults. During handling, personnel should not approach the surge arrester. The method of using circuit breakers or manual grounding transfer can be used to disconnect the faulty surge arrester.
3. The surge arrester suddenly explodes during operation. In this case, if it has not caused permanent system grounding, the faulty phase surge arrester can be shut down by opening the isolating switch of the faulty phase after thunderstorms, and a qualified surge arrester should be replaced in time. If the arrester has been burned and exploded and has caused permanent system grounding, it is prohibited to use the operation of the isolating switch to shut down the faulty surge arrester.
4. The internal indicator of the surge arrester burns black or is burned out, the connection point of the grounding lead-down line is broken, the valve plate resistance of the surge arrester fails, the arc extinguishing characteristics of the spark gap deteriorate, the power frequency continuation current increases. If any of the above abnormal phenomena occur, the surge arrester should undergo electrical tests or disassembly inspection in a timely manner.
English
Spanish
Russian