How To Deal With Poor Contact Of Transformer Tap Changer?

How To Deal With Poor Contact Of Transformer Tap Changer?

1. Severe damage to the contacts
Solution: Remove the contacts, replace them with new ones or reassemble them as they were.

2. Unequal contact pressure
Some tap changers have adjustable contact spring. Adjust the spring appropriately to maintain balanced contact pressure. The surface roughness of the contacts should be suitable. No polishing or grinding is necessary.

3. Remove oxide film and dirt
Over time, the contacts of the tap changer will be covered with an oxide film and dirt.
Solution:
If the oxide film is thin and the dirt is not much, switching the contacts back and forth at each position several times will remove it. If it is more, then use gasoline to scrub.
Sometimes, decomposition products of the insulating oil deposit on the contacts in the form of a shiny film. The surface is very clean, but it is actually an insulating layer, which will hinder contact. You can use acetone to scrub it off and it will be removed.