How to Detect and Determine the Fault of the Secondary Open Circuit of a Current Transformer?

1. The instrument indication in the circuit is abnormal, usually decreasing or becoming zero. When the current circuit of the measuring instrument is open, it will cause inconsistent indications of the three-phase current meters, reduced power meter indications, slow or no rotation of the metering instrument. If the instrument indication is intermittent, it may be in a semi-open circuit state (due to poor contact).
2. Whether there is noise from the CT body, such as a buzzing sound, uneven vibration, severe heating, or smoke emission. Of course, these phenomena are not obvious when the load is small.
3. There are discharge and arcing phenomena at the terminals of the CT secondary circuit or at the wire heads of the components.
4. If there is a misoperation or refusal to operate of the relay protection, this can be detected and handled during a mis-trip or over-trip.
5. The watt-hour meter and relay burn out and smoke. Whether the reactive power meter and the watt-hour meter, the remote device’s transducer, and the protection device’s relay burn out will not only cause the secondary open circuit of the CT but also cause the secondary short circuit of the PT.
These are just some basic clues for checking the secondary open circuit of the CT. In fact, during normal operation, when the primary load is not large, the secondary is not in use, and it is not the open circuit of the measurement current circuit, the secondary open circuit fault of the CT is not easy to be detected. The detection and handling of the secondary open circuit fault of the CT should try to reduce the primary load current to lower the voltage of the secondary circuit.
During operation, pay attention to safety. Stand on an insulating pad, wear insulating gloves, use well-insulated tools, and do the following points:
1. When discovering the secondary open circuit of the CT, first determine which current circuit is faulty, the phase of the open circuit, and whether it has an impact on protection, report to the dispatch, and deactivate the possibly erroneous protection;
2. Try to reduce the primary load current. If the CT is severely damaged, transfer the load and power off for handling;
3. Try to find a way to short-circuit the CT secondary circuit at the nearby test terminals according to the drawing using good shorting wires, then check and handle the open circuit point;
4. If sparks are found during shorting, then the shorting should be effective, and the fault point should be below the short-circuit point in the circuit, and further search can be conducted. If no sparks are found during shorting, then the fault point may be in the circuit before the short-circuit point, and the short-circuit point can be gradually changed forward to narrow the range for inspection;
5. Within the fault range, check the easily faulty terminals and components. For the detected faults, if they can be handled by themselves, such as loose or poor contact of external components like connection terminals, immediately handle and put the withdrawn protection back into operation. If the open circuit point is on the connection terminals of the CT body, then power off for handling. If it cannot be handled by themselves (such as inside the relay) or the fault cannot be identified by themselves, report to the superior first after shorting the secondary of the CT.