Air Guide Box/Gas Sampling Devices for Use with Buchholz Relays on Power Transformers

Air Guide Box/Gas Sampling Devices for Use with Buchholz Relays on Power Transformers

Thus ubstruction manual is usded for connecting the air relay on the upper part of the air guide box and transformer and discharging oil and taking air.

 

Structure and Working Principle(See Fig.1)

This air guide box is a closed structure. See Figure 1. ltem 1 (connecting tube) is connected to ltem 7 (air relay discharge cock) through ltem 8 (upper nut ) and to ltem 6(air guide box) through the lower part. The air guide box is mounted on the oil tank wall of the transformer. The air inside the aie relay is filled into the air guide box through the connecting tube to take the air on the ground at any time.

 

Intallation and maintenance (See Fig.1)

When installing and using this air guide box, one end of ltem 1(connecting tube) should first be connected to the air guide box. Then , the copper tube should bebent slowly along the oil tank of the transformer to the air relay and air-take cock. After the nut and valve needle are removed from the air-take cock, ltem 8 (nut) should be tightened onto the cock seat. (The copper tube must not be flattened.)

 

Taking air

When taking air, ltem 4 (lower air-take cap ) should be first loosened,then, ltem 3 (lower air-take nut ) is slightly turened to discharge the oil inside the air guide box. When the oil level drops, ltem 6 (air guide box ) is supplemented with the air inside the air relay through ltem 1 (connecting tube).When the required air volume can be seen from the sight glass, ltem 3 (lower air-take nut )should be tightened. Ltem 2 (upper air-take cap) can be loosened in the same way. After connecting the air-take container, ltem 3 (upper air-take nut ) should be slightly turned so that the air is filled into the container. Then ,the nut is tightened again for sealing.

1. connecting tube 2. upper air-take cap 3. upper air-take nut 4. lower air-take nut 5. lower air-take cap 6. air guide box

7. relay junction 8. nut 9. window 10. air guide box junction

 

Note: The length of the connecting tube should be indicated when ordering the product.