E63L-C Earth Leakage Circuit Breaker

E63L-C Earth Leakage Circuit Breaker

Category:

Product parameterse

1P+N 3P+N 3P
Size(mm) 72 126

117

Module

4modules 7modules 6.5modules
Characteristics Overload protection, short-circuit protection, leakage protection, power outage trip, automatic reclosing on power recovery, overvoltage/ undervoltage protection (optional)

Overload protection, short-circuit protection, leakage protection, power outage trip, automatic reclosing on power recovery, overvoltage/ undervoltage protection (optional), Phase monitoring & phase sequence protection (optional)

Wiring method

Top incoming/bottom outgoing (w/wiring mark), naught wire mark Top incoming/ bottom outgoing (w/wiring mark)
Rated current (A)

1、2、4、6、10、16、20、25、32、40、50、63

Rated leakage current (mA)

10、30、100、300、500
Leakage trip type

AC type, A type

Rated voltage (V) Un

230 400
Rated insulation voltage (V) Ui

500

Overvoltage (V) Uve (optional)

275±5V 460±5V
Undervoltage (V) Uoe (optional) 165±5V

290±5V

Power outage trip

Optional configuration
Phase monitoring /

Optional configuration

Phase sequence protection

/ Optional configuration
Reclosing time on power recovery

To be set as required

Rated operating frequency (Hz)

50/60
Rated impulse withstand voltage (V) Uimp

4000

Rated short-circuit capacity Icn

6000
Rated short-circuit breaking capacity Ics

6000

Overvoltage type

Ⅱ
Pollution capacity

2

Instantaneous

trip

characteristics

B(3In-5In) Yes

C(5In-10In)

Yes

D(10In-20In)

Yes

Electric shock protection level

Ⅱ
Mechanical service life

20000

Protection level

Circuit breaker IP20
Installed in the

distribution box

IP40

Max. wiring capacity (²)

50
Terminal maximum torque (Nm)

5

    has been added to your cart: