E63L Earth Leakage Circuit Breaker

E63L Earth Leakage Circuit Breaker

Category:

Type A & Type AC

Product parameters

1P+N 3P+N 3P

Size(mm)

36 81 72
Module 2

modules

4.5

modules

4

modules

Characteristics

Short circuit protection, overload

protection, leakage protection, N-pole

with breaking capacity

Short circuit protection, overload protection, and  leakage protection
Wiring method Top incoming/bottom outgoing (w/wiring

mark),

naught wire mark

Top incoming/

bottom outgoing

(w/wiring mark)

Rated current (A)

1、2、4、6、10、16、20、25、32、40、50、63
Rated leakage current (mA)

10、30、100、300、500

Leakage trip type

AC type, A type
Rated voltage (V) Un 230

400

Rated insulation voltage (V) Ui

500 500
Rated operating frequency (Hz)

50/60

Rated impulse withstand voltage (V) Uimp

4000
Rated short-circuit capacity Icn

6000

Rated short-circuit breaking

capacity Ics

6000
Overvoltage category

Ⅱ

Pollution capacity

2

Instantaneous

tripping

characteristics

B(3In-5In)

Yes
C(5In-10In)

Yes

D(10In-20In)

Yes

Electric shock protection level

Ⅱ
Mechanical characteristics mechanical life

20000

Protection

level

Circuit breaker IP20
Installed in the

distribution box

IP40

Maximum wiring capacity(²)

50
Terminal ultimate torque (Nm)

5

 

Type B

Product parameters

1P+N 3P+N 3P

Size(mm)

54 90

90

Module

3

modules

5

modules

5

modules

Characteristics Short circuit protection, overload

protection, leakage protection, N-pole

with breaking capacity

Short circuit protection, overload protection, and  leakage protection

Wiring method

Top incoming/bottom outgoing (w/wiring

mark),

naught wire mark

Top incoming/

bottom outgoing

(w/wiring mark)

Rated current (A)

1、2、4、6、10、16、20、25、32、40、50、63

Rated leakage current (mA)

10、30、100、300、500
Leakage trip type

B type

Rated voltage (V) Un

230 400
Rated insulation voltage (V) Ui 500

500

Rated operating frequency (Hz)

50/60
Rated impulse withstand voltage (V) Uimp

4000

Rated short-circuit capacity Icn

6000
Rated short-circuit breaking

capacity Ics

6000

Overvoltage category

Ⅱ
Pollution capacity

2

Instantaneous

tripping

characteristics

B(3In-5In)

Yes

C(5In-10In)

Yes

D(10In-20In)

Yes

Electric shock protection level

Ⅱ

Mechanical characteristics mechanical life 20000

Protection

level

Circuit breaker IP20
Installed in the

distribution box

IP40

Maximum wiring capacity(²)

50

Terminal ultimate torque (Nm)

5

    has been added to your cart: