E63M-T Miniature Circuit Breaker

E63M-T Miniature Circuit Breaker

Category:

Product parameters

2P 3P 4P
Size(mm) 54 72

90

Module

3modules 4modules 5modules
Characteristics Overload protection, short circuit protection, power outage and trip protection, overvoltage and undervoltage protection (optional)

Overload protection, short circuit

protection, power outage and

trip protection, overvoltage and

undervoltage protection (optional), Phase monitoring&Phase sequence

protection

Wiring method

Top incoming/bottom outgoing (w/wiring mark)
Rated current (A)

1、2、4、6、10、16、20、25、32、40、50、63

Rated voltage (V) Un

230 400
Rated insulation voltage (V) Ui 500

500

Overvoltage (V) Uve (optional)

275±5V 460±5V
Undervoltage (V) Uoe (optional) 165±5V

290±5V

Power outage and trip

Optional
Phase monitoring /

Optional

Phase sequence protection

/ Optional
Rated operating frequency (Hz)

50/60

Rated impulse withstand voltage (V)

Uimp

4000
Rated short-circuit capacity Icn

6000

Rated operation short-circuit breaking capacity Ics

6000

Overvoltage category

Ⅱ
Pollution capacity

2

Instantaneous

tripping

characteristics

B(3In-5In)

Yes

C(5In-10In)

Yes

D(10In-20In)

Yes

Electric shock protection level

Ⅱ
Mechanical service life

20000

Protection level

Circuit breaker IP20
Installed in the

distribution box

IP40

Max. wiring capacity(²)

50
Terminal maximum torque (Nm)

5

    has been added to your cart: