Natural ester insulating oil meets IEC/ASTM/IEEE standards.
Advantages:
1.Good low temperature performance
2.Reliable oxidation resistance
3.Excellent fire resistance and electrical performance, etc.
Application:
It can instead of mineral oil as the insulation medium of transformers and similar electrical equipments.
Typical data
|
PROPERTY |
Typical data | LIMITS | TEST
METHOD |
||
| Physical | Appearance | Clear, free from
sediment and suspended matter |
Clear, free from sediment and suspended matter | Visualization | |
| Pour point, ℃ | -21 | ≤-10 | ISO 3016 | ||
| Density(20℃), kg/m³ | 916.7 | ≤1000 | ISO 3675 | ||
| Viscosity(40℃), mm²/s | 31.84 | ≤50 | ISO3104 | ||
| Electrical | Dissipation factor(90℃) | 0.006 | ≤0.05 | IEC 60247 | |
| Breakdown voltage, kV | 70 | ≥35 | IEC 60156 | ||
| Chemical | Soluble acidity, mgKOH/g | 0.026 | ≤0.06 | IEC62021-3 | |
| Oxidation stability 120℃/48h | |||||
| Total acidity, mgKOH/g
DDF(90℃) Viscosity(40℃) |
0.04
0.11 15.7 |
≤0.6
≤0.5 ≤30%increase |
IEC61125-
Method C |
||
| Health, safety and environment | Flash point, ℃ | 258 | ≥250 | ISO 2719 | |
| Fire point, ℃ | 360 | ≥300 |
ISO 2592 |
||