Split Core Current Transformers ( Rectangular)
- Description
- Inquiry
Description
1. Features:
1). Delicate, exquisite and light, conveniently to install
2). Separated coil、Low consumption with magnetic
3). Easily install, no necessaries to disconnect primary busbar, measuring with power on, safety and convenient.
2. Typical Application
Multi function electricity energy meter and field calibrator, instruments
Used in the measurement and protection in power system, while the mobility is strong or space is narrow or power system is uninterrupted
3. Dimension:
Model Number |
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
K |
CY-KCT-02-223 |
20 |
30 |
50 |
89 |
110 |
34 |
47 |
40 |
32 |
52.5 |
67.5 |
CY-KCT-02-258 |
50 |
80 |
78 |
114 |
145 |
32 |
32 |
32 |
33 |
52.5 |
67.5 |
CY-KCT-02-288 |
80 |
80 |
108 |
144 |
145 |
32 |
32 |
32 |
33 |
52.5 |
67.5 |
CY-KCT-02-812 |
80 |
120 |
108 |
144 |
185 |
32 |
32 |
33 |
33 |
52.5 |
67.5 |
CY-KCT-02-816 |
80 |
160 |
120 |
184 |
245 |
52 |
47 |
52 |
38 |
61.00 |
76 |
4. Electrical Parameter
Model Number |
Primary current(A) |
Secondary current (A) |
Burden(VA) |
Size of window mm |
Net weight |
||
Class 0.5 |
Class 1 |
Class 3 |
|||||
CY-KCT-02-223 |
100 |
5A/1A |
/ |
/ |
1.5 |
20×30 |
0.75 |
150 |
5A/1A |
/ |
/ |
3 |
|||
200 |
5A/1A |
/ |
2.5 |
3.75 |
|||
250 |
5A/1A |
/ |
3.75 |
5 |
|||
CY-KCT-02-258 |
300 |
5A/1A |
/ |
3.75 |
5 |
50×80 |
0.90 |
400 |
5A/1A |
2.5 |
3.75 |
7.5 |
|||
500 |
5A/1A |
3.75 |
5 |
10 |
|||
600 |
5A/1A |
5 |
7.5 |
15 |
|||
CY-KCT-02-288 |
800 |
5A/1A |
5 |
7.5 |
15 |
80×80 |
1.25 |
1000 |
5A/1A |
10 |
15 |
15 |
|||
CY-KCT-02-812 |
1200 |
5A/1A |
15 |
20 |
30 |
80×120 |
1.25 |
1500 |
5A/1A |
15 |
20 |
30 |
|||
1600 |
5A/1A |
15 |
20 |
30 |
|||
CY-KCT-02-816 |
2000 |
5A/1A |
25 |
30 |
45 |
80×160 |
4.30 |
2500 |
5A/1A |
||||||
3000 |
5A/1A |
||||||
4000 |
5A/1A |
||||||
5000 |
5A/1A |
||||||
6000 |
5A/1A |
Remarks: If secondary current is “mA”, Can adjust turns ratio and burden as per customers’ requirements.