- Description
- Inquiry
Synthetic ester insulating oil is an unused synthetic ester insulating oil. It is a polyol ester synthesized by pentaerythritol and mixed fatty acids instead of mineral oil as an insulating medium for transformers and similar insulating equipment.
Advantage:
It has good electrical insulation properties, excellent oxidation resistance and moisture resistance while it is safe, environmentally friendly and easy to biodegrade.
Typical data
| IEC 61099 | MIDEL7131 | JSSJ-SE-1 | |||
|
PROPERTY |
Test method | Un-used new fluid property requirements | Typical Values |
Typical Values |
|
|
Physical |
|||||
|
Colour |
ISO 2211 |
≤200 Hazen |
125 |
||
|
Appearance |
Clear, free from water and suspended matter and sediment |
Clear, free from water and suspended matter and sediment |
Clear, free from water and suspended matter and sediment |
||
|
Density at 20℃ |
ISO 3675or ISO 12185 | ≤1 |
0.97 |
0.97 |
|
|
Kinematic Viscosity (mm²/sec) |
At 40℃ | ISO 3104 | ≤35 |
29 |
34 |
|
At -20℃ |
≤3000 |
1440 |
2002 |
||
|
Flash Point PMCC(℃) |
ISO 2719 | ≥250 | 260 |
262 |
|
|
Fire Point(℃) |
ISO 2592 | ≥300 |
316 |
>310 |
|
|
Pour Point(℃) |
ISO 3016 | ≤ -45 | -56 |
-54 |
|
|
Crystallization |
IEC 61099(2010 Annex A) | No crystals | No crystals | No crystals | |
| Biodegradation | Readily Biodegradable | Readily Biodegradable |
Readily Biodegradable |
||
|
Electrical |
|||||
|
Dielectric Breakdown(kV) |
IEC60156 | ≥45 | >75 |
>75 |
|
|
Power Factor at 90℃ |
IEC60247 | ≤0.03 | <0.008 |
<0.01 |
|
|
DC Resistvityat90°C(GΩ.m) |
IEC 60247 | ≥2 | >20 |
>18 |
|
|
Chemical |
|||||
|
Water Content(mg/kg) |
IEC60814 | ≤200 | 50 |
50 |
|
|
Acidity(mg KOH/g) |
IEC62021-1 or2 | ≤0.03 |
<0.03 |
0.01 |
|
|
Oxidation Stability(164 hr) |
IEC61125C |
||||
|
Total Acidity(mg KOH/g) |
≤0.3 |
0.02 |
0.02 |
||
| Total Sludge(9% mass) | ≤0.01 | ≤0.01 |
≤0.01 |
||
English
Spanish