Special Accidents and Maintenance Methods for Three-phase Combined Surge Arresters (also known as overvoltage protectors)

a. Inter-phase flashover caused by crossed two-phase insulated cables.
Symptom: The upper end of the surge arrester is blackened, and the system has a phase-to-phase short circuit.
Conclusion: Crossed two-phase insulated cables cause inter-phase surface flashover.
Treatment: Separate the two-phase insulated cables to a certain distance.
b. Inter-phase breakdown.
Symptom: The upper end of the surge arrester is blackened, and the system has a phase-to-phase short circuit.
Conclusion: Due to the limited space inside the cabinet, the three phases of the surge arrester did not align with the busbar, and the distance between the high-voltage end of one phase of the surge arrester and the busbar of another phase was too close, resulting in air discharge.
Treatment: When the cabinet space is too narrow, use a three-column type product with the grounding electrode of the four-stage surge arrester buried in the base to ensure alignment with the busbar.
c. Accidents caused by the short circuit of the common neutral point of the outdoor combined surge arrester.
Symptom: The common neutral point of the surge arrester arcs to ground.
Conclusion: The common neutral point of the surge arrester is not a constant zero potential point. During operation, the potential is relatively high, which easily leads to ground discharge.
Treatment: Keep the common neutral point of the surge arrester at a sufficient distance from the surrounding zero potential points.
d. Accidents caused by frequent operation.
Symptom: The service life of the surge arrester decreases rapidly.
Conclusion: Since the three-phase combined surge arrester is also used to prevent operational overvoltage, it has a heavier burden than ordinary surge arresters. Frequent operation can easily affect the service life.
Treatment: Connect the surge arrester with gaps; in environments with frequent operation, the expected service life of the combined surge arrester should be estimated based on the actual situation (conventional surge arresters for lightning protection have an expected service life of generally 20 years), and after the expected service life is reached, strengthen detection or directly replace it.