Substation DC System Grounding Fault Causes and Handling Methods

1. Several Causes of DC System Grounding in Substations
(1) During the rainy season, moisture in outdoor terminal boxes or mechanism boxes causes the insulation resistance of the positive or negative power supply in the DC secondary circuit to decrease, and in severe cases, it may drop to zero, thereby forming a ground.
(2) For some models of circuit breaker switches, the connecting plugs or sockets of the movable and fixed parts lack reliable insulation isolation measures. When the circuit breaker moves back and forth, it causes the wires to be damaged, thereby causing the DC circuit to come into contact with the metal part of the switch, resulting in grounding.
(3) For some DC systems that have been in operation for many years, the insulation of secondary equipment has aged and become damaged, making it prone to grounding.
(4) Due to non-strict construction techniques, there are exposed wires or wire ends touching the cabinet body in the DC circuit, causing grounding.
2. Basic Principles and Methods for Locating Grounding Faults
(1) General Handling Principles: Based on the on-site operation mode, operation conditions, and climatic influence, determine the possible grounding location. Follow the principle of first outdoors then indoors, first closing then control, from the main power supply to the branch power supply, gradually narrowing the scope. Use methods such as pulling circuits to find and handle the problem. Note: Do not cut off each dedicated DC circuit for too long (generally no more than 3 seconds). Regardless of whether the circuit is grounded or not, it should be closed.
(2) Specific Handling Methods: First, understand the composition of the on-site DC power supply system. Through the DC system insulation monitoring device or grounding test button, preliminarily determine whether it is the positive or negative DC ground (assuming the insulation monitoring is reliable and assuming positive grounding).
Then, immediately cut off all closing power supply switches. If the grounding signal disappears, it indicates that the grounding point is in the closing circuit. Use the same method to pull and open the closing circuit of the station’s closing circuit or remove the positive power supply end of the main power supply to conduct a branch inspection and judgment; if the monitoring device still reports grounding, it indicates that the grounding point is in the control, signal, etc. circuits. Then, further use the same method to check the DC screen, battery cabinet, and each protection screen, control screen, signal screen and their control circuits in the station.
After identifying which output power circuit the grounding point belongs to, quickly pull open the DC load switch of the grounding circuit or remove the positive power supply fuse in the circuit, and based on the alarm situation of the insulation monitoring device, determine whether the grounding point is before or after the switch (fuse).
After clarifying the situation, quickly remove the positive terminals of related equipment within the range and observe the alarm signal to determine whether the grounding point is within this part of the equipment.
Then, continue to follow the above principles and methods to gradually narrow the search range until the grounding point is found.
There are many factors causing DC system grounding in substations. In daily operation and maintenance, different measures should be taken according to specific circumstances:
(1) Strictly control the construction techniques of secondary equipment, exert subjective initiative, and reduce the probability of grounding faults. For example, strengthen sealing of outdoor terminal boxes and mechanism boxes, install anti-moisture and dehumidification equipment or materials; take measures to improve the insulation performance of the movable parts of circuit breaker switches, such as wrapping the wire ends with insulating materials, to avoid grounding caused by the random movement of the circuit breaker; for control cables and related secondary equipment that have aged insulation and cannot meet the requirements for insulation resistance to ground, replace them in time.
(2) Strengthen the operation and maintenance management of primary equipment such as circuit breakers, disconnectors, and circuit breaker switches. Strictly follow the operation procedures for equipment with mechanical transmission parts to avoid grounding faults caused by unreasonable operation.
(3) When searching and handling grounding faults, strictly follow the requirements of relevant electrical equipment maintenance and operation regulations and combine with the actual conditions on site.
Do not work alone. Do not allow the DC power supply to stop running for a long time (especially when the weather conditions do not permit). The time for removing and restoring each terminal and each switch should be as short as possible.