The phenomenon of secondary open circuit of current transformer
A secondary open circuit of current transformer will cause the magnetic flux in the iron core to increase sharply (up to 10 to 20 times the normal operating magnetic flux), resulting in severe saturation of the iron core. It will generate a very high voltage, posing a threat to equipment and personnel. The iron core loss will increase, causing severe heating and even burning.
If the intermittent open circuit is caused by loose screws, there will be phenomena such as sparking at the connection terminals, oscillation of the current meter, and a dull sound from the transformer.

 

Reasons for the secondary open circuit of the current transformer:
1. The screw of the AC connection terminal is not in good contact with the pressed hole, and it is in a half-open state;
2. The metal terminal of the AC connection piece is not sufficiently pressed in;
3. During maintenance, the relay connection terminals were not properly connected or the test disconnect terminal was not restored;
4. The secondary terminals have been loose for a long time, resulting in excessive heating or oxidation-induced overheating and opening circuit;
5. The outdoor terminal box was damp and the terminals were severely rusted, causing poor contact.